Fluke 378 FC 1000A AC/DC Non-Contact Voltage True-rms Clamp Meter with iFlex
1000A AC/DC Trms Noncontact Vol Wireless Clamp,Pq Ind,Iflex
Order #: 378-FC
Mfg #: 5111812
Special Price
$1,061.15
Regular Price
$1,264.79
Fluke 378 FC 1000A AC/DC Non-Contact Voltage True-rms Clamp Meter with iFlex
1000A AC/DC Trms Noncontact Vol Wireless Clamp,Pq Ind,Iflex
Order #: 378-FC
Mfg #: 5111812
Special Price
$1,061.15
Regular Price
$1,264.79
Availability:
In stock
Product Highlights
The Fluke 378 FC is a true-rms clamp meter that use FieldSense™ technology to make testing faster and safer, all without touching a live conductor. You get accurate voltage and current measurements through the clamp jaw. Simply clip the black test lead to any electrical ground, put the clamp jaw around the conductor and see reliable, accurate voltage and current values on the display.
- Measure voltage and current with your clamp jaw
- Faster, safer testing - all without touching a live wire - using FieldSense™ technology
- Complete 3-phase voltage and current tests with fewer steps
- Power quality indicator shows whether equipment or power line is faulty (378 FC)
Key Attributes
- AC Current: Jaw: 999.9 A, 2% accuracy
- AC Voltage: Field Sense: 1000 V, 3% accuracy
- AC Current: Flexible Current Probe: 2500 A, 3% accuracy
- AC or DC Voltage: Test Leads: 1000 V, 1% accuracy
- Fluke Toolpak Meter Hanging KitMeter Hanging Kit
Order #: TPAK80-4
Mfg #: 1281997
Availability:In stockSpecial Price $62.74 Regular Price $74.79 - Fluke PRV240 Battery-powered voltage source proving unitBattery-powered voltage source proving unit
Order #: PRV240
Mfg #: 4566209
Availability: Ships in 3-4 weeksSpecial Price $228.19 Regular Price $271.99
General specifications | |
---|---|
General Maximum voltage (between any terminal and earth ground) | 1000 V |
Battery | Type 2 AA IEC LR6 alkaline |
Life | 200 hours |
Display | Dual readout |
Automatic Power Off | 20 minutes |
AC Current: Jaw | |
Range | 999.9 A |
Resolution | 0.1 A |
Accuracy | 2 % ± 5 digits (10 Hz to 100 Hz) |
2.5 % ± 5 digits (100 Hz to 500 Hz) | |
Crest Factor (50/60 Hz) | 3 @ 500 A |
2.5 @ 600 A | |
1.42 @ 1000 A | |
Add 2 % for C.F. >2 | |
AC Current: Flexible Current Probe | |
Range | 2500 A |
Resolution | 1 A (≤ 2500 A) 0.1 A (≤ 999.9 A) |
Accuracy | 3 % ±5 digits (5 Hz to 500 Hz) |
DC Current | |
Range | 999.9 A |
Resolution | 0.1 A |
Accuracy | 2 % ±5 digits |
AC Voltage: FieldSense | |
Range | 1000 V |
Resolution | 1 V (≤ 1000 V) |
Accuracy | |
≤ 4/0 AWG | 3 % ±5 digits (45 Hz to 66 Hz) |
≥ 4/0 AWG | 5 % ±5 digits (45 Hz to 66 Hz) |
AC Voltage: Test Leads | |
Range | 600.0 V 1000 V |
Resolution | 0.1 V (≤ 600.0 V) |
1 V (≤ 1000 V) | |
Accuracy | 1 % ±5 digits (20 Hz to 500 Hz) |
DC Voltage | |
Range | 600.0 V |
1000 V | |
Resolution | 0.1 V ≤ 600.0 V) |
1 V (≤ 1000 V) | |
Accuracy | 1 % ± 5 digits |
mV dc | |
Range | 500.0 mV |
Resolution | 0.1 mV |
Accuracy | 1 % ± 5 digits |
Amps Frequency: Jaw | |
Range | 5.0 Hz to 500.0 Hz |
Resolution | 0.1 Hz |
Accuracy | 0.5 % ± 5 digits |
Trigger Level | 5 Hz to 10 Hz, ≥ 10 A |
10 Hz to 100 Hz, ≥ 5 A | |
100 Hz to 500 Hz, ≥ 10 A | |
Amps Frequency: Flexible Current Probe | |
Range | 5.0 Hz to 500.0 Hz |
Resolution | 0.1 Hz |
Accuracy | 0.5 % ±5 digits |
Trigger Level | 5 Hz to 20 Hz, ≥ 25 A |
20 Hz to 100 Hz, ≥ 20 A | |
100 Hz to 500 Hz, ≥ 25 A | |
Resistance | |
Range | 60.00 kΩ |
6000 Ω | |
600.0 Ω | |
Resolution | 0.1 Ω (≤ 600.0 Ω) |
1 Ω (≤ 6000 Ω) | |
10 Ω (≤ 60.00 kΩ) | |
Accuracy | 1 % ±5 digits |
Capacitance | |
Range | 1000 µF |
Resolution | 0.1 µF (≤ 100.0 µF) |
1 F (≤ 1000 µF) | |
Accuracy | 1% ±4 digits |
Mechanical | |
Size (L x W x H) | 274 mm x 86 mm x 47 mm |
Weight (with Batteries) | 463 g |
Jaw Opening | 34 mm |
Flexible Current Probe Diameter | 7.5 mm |
Flexible Current Probe Cable Length (head to electronics connector) | 1.8 m |
Rogowski Coil Length | 450 mm |
Environmental | |
Operating Temperature | -10 °C to 50 °C |
Storage Temperature | -40 °C to 60 °C |
Operating Humidity (without condensation) | Non condensing (<10 °C) |
≤ 90 % RH (10 °C to 30 °C) | |
≤ 75 % RH (30 °C to 40 °C) | |
≤ 45 % RH (40 °C to 50 °C) | |
Temperature Coefficients | Add 0.1 x specified accuracy for each degree C >28 °C or <18 °C |
Ingress Protection | IEC 60529: IP30 (jaw closed) |
Operating Altitude | 2000 m |
Storage Altitude | 12 000 m |
Electromagnetic Compatibility (EMC) | |
International | IEC 61326-1: Portable Electromagnetic Environment |
IEC 61326-2-2, CISPR 11: Group 1, Class B | |
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | |
Class B: Equipment is suitable for use in domestic establishments and in establishments directly connected to a low voltage power supply network which supplies buildings used for domestic purposes. | |
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. | |
Korea (KCC) | Class A equipment (Industrial Broadcast & Communications Equipment) |
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | |
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. |
Safety | |
General | IEC 61010-1: Pollution degree 2 |
Measurement | IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V |
IEC 61010-2-033: CAT III 1000 V / CAT IV 600 V | |
Current Clamp for Leakage Current Measurements | IEC 61557-13: Class 2, ≤ 30 A/m |
Wireless Radio | |
Radio Frequency Certification | FCC ID: T68-FBLE IC:6627A-FBLE |
Frequency Range | 2405 MHz to 2480 MHz |
Output Power | <100 mW |